Device TypeVariantsModbus TCP (Ethernet)RS485Curtailment
SG04LP3-EUSUN-5/6/8/10/12K
SG01LP1-EUSUN-12/14/16K

接线

RS485

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
引脚 1 / Modbus-485_B RS485 ARS485_POSRS485 ATX+
引脚 2 / Modbus-485_A RS485 BRS485_NEGRS485 BTX-
引脚 3 / GND_485 RS GNDGNDNot availableG
Image 1
Image 1
Image 1

配置

NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.

转到“主屏幕” >> “系统设置” >> “高级功能。”

  • Modbus SN 应设置为 1 到 247 之间的任何数字。请不要选择 0!!请注意,如果 RS485 总线上有多个设备,则每个设备应具有唯一的编号。这是地址。
  • 应检查从设备。
  • 只有在额外的计量仪器直接连接到逆变器时,才应勾选 “EX_meter For CT”。如果只有一个表与 SmartgridOne Controller 并联,应该取消勾选。
  • 确保以下设置均正确:“最大充电电流”,“最大放电电流”,“电网充电安培”