Saltar al contenido principal

Power-Sonic

logo

Dispositivos Soportados

Device TypeModbus TCP (Ethernet)RS485Curtailment
PS-PULSE-INV-6KW
PS-PULSE-INV-8KW
PS-PULSE-INV-10KW
PS-PULSE-INV-12KW

Cableado

RS485

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
RS485 ARS485_POSRS485 ATX+
RS485 BRS485_NEGRS485 BTX-
RS GNDGNDNot availableG
Image 1

Configuración

NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
  1. Establezca el modo de trabajo en Autoconsumo
Image 1
  1. Establezca Exportación Cero en Desactivar
Image 1
  1. Establezca Control Remoto en Habilitar
Image 1
  1. Establezca la dirección RS485. La tasa de baudios predeterminada es 9600, si no, configúrela en 9600.
Image 1
  1. Establezca la corriente de carga. Establezca la corriente de carga.
IMPORTANTE!

Para un 5KT configúrelo en 100 Para un 10KT configúrelo en 160

Image 1
  1. Establezca AC Acoplar en Habilitar
Image 1