Aller au contenu principal

DEYE

logo

Appareils pris en charge

Device TypeVariantsModbus TCP (Ethernet)RS485Curtailment
SG04LP3-EUSUN-5/6/8/10/12K
SG01LP1-EUSUN-12/14/16K

Câblage

RS485

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
Pin 1 / Modbus-485_B RS485 ARS485_POSRS485 ATX+
Pin 2 / Modbus-485_A RS485 BRS485_NEGRS485 BTX-
Pin 3 / GND_485 RS GNDGNDNot availableG
Image 1
Image 1
Image 1

Configuration

NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.

Allez dans “Écran principal” >> “Paramètres du système” >> “Fonction avancée.”

  • Le SN Modbus doit être réglé sur un nombre entre 1 et 247. Ne choisissez pas 0 !! Notez que s'il y a plusieurs appareils sur le bus RS485, chacun doit avoir un numéro unique. C'est l'adresse.
  • L'esclave doit être coché.
  • Ce n'est que lorsque un compteur supplémentaire est connecté directement à l'onduleur que “EX_meter For CT” doit être coché. S'il n'y a qu'un seul compteur en parallèle avec le SmartgridOne Controller, cela doit être décoché.
  • Assurez-vous que les paramètres suivants sont tous corrects : "Max A Charge", "Max A Discharge", "Ampère de charge de la grille"
Image 1