Chint Energy Meters

Supported Devices

Meter TypeVariantsModbus TCPRS485
DDSU666230V-5/80A
230V-100A/40mA
DTSU6663x230V/400V-5/80A
3x230V/400V-1.5(6)A
3x230V/400V-100A/40mA
DTSU666HW3x230V/400V-5/80A
3x230V/400V-1.5(6)A
3x230V/400V-100A/40mA

Connection

The communication between the SmartgridOne and the energy meter operates via an RS-485 serial bus or Modbus TCP.

It is recommended to use shielded cables with twisted pairs for optimal performance. For short distances, a twisted pair from a network cable (minimum CAT5e) can be used.

The following guidelines apply:

  • Maximum Distance: The total cable length, including the main cable and branches, is limited to 100 meters.
  • Connecting Multiple Energy Meters: The cable should be daisy-chained from meter to meter or branched off the main cable (branches must not exceed 1 meter).
  • Long Distances: It is recommended to install a 120Ω termination resistor at the end of the main cable and activate the termination resistor on the SmartgridOne Controller.

Example of cable setup:

Cable WireEnergy MeterSmartgridOne ControllerRS485 USBSolar Gateway
White-BrownTerminal 24Terminal RS485 ATerminal RS485 ATerminal RS485 A
BrownTerminal 25Terminal RS485 BTerminal RS485 BTerminal RS485 B
ShieldNot ApplicableTerminal RS485 GNDTerminal RS485 GNDTerminal RS485 GND

Chint Wiring