Power-Sonic

logo

Dispositivos Suportados

Device TypeModbus TCP (Ethernet)RS485Curtailment
PS-PULSE-INV-6KW
PS-PULSE-INV-8KW
PS-PULSE-INV-10KW
PS-PULSE-INV-12KW

Fiação

RS485

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSmartgridOne Controller model OM1SmartgridOne Controller model IG8RS485-USB converterRS485-Ethernet converter
RS485 ARS485_POSRS485 ATX+
RS485 BRS485_NEGRS485 BTX-
RS GNDGNDNot availableG
Imagem 1

Configuração

NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
  1. Configure o modo de operação para Auto Consumo
Imagem 1
  1. Configure a Exportação Zero para Desativar
Imagem 1
  1. Configure o Controle Remoto para Ativar
Imagem 1
  1. Configure o endereço RS485. A taxa de transmissão padrão é 9600; se não for, defina para 9600.
Imagem 1
  1. Configure a corrente de carga. Configure a corrente de carga.
IMPORTANTE!

Para um 5KT, defina para 100 Para 10KT, defina para 160

Imagem 1
  1. Configure o Acoplamento CA para Ativar
Imagem 1