Victron

Supported Devices

Device TypeModbus TCP (Ethernet)RS485Curtailment
Multiplus II
Multiplus RS
Cerbo GX
Venus GX
Inverters with built in GX device
Other Victron devices
Important

If you already have your PV or other devices connected to the Victron system make sure not to add them again to the SmartgridOne Controller. This can cause double measurements.

Wiring

For correct ethernet wiring: Follow the the guidelines for ethernet wiring.

Video

Configuration

1. Modbus TCP must be enabled.

In the settings of the inverter:

  1. Go to "Settings"
  2. Go to "Services"
  3. Go to "Modbus TCP"
  4. Select "Enable Modbus/TCP."
Image

2. The ESS must be in a mode that allows steering. In the inverter settings, go to:

  1. Go to "Settings"
  2. Go to "ESS"
  3. Select mode "Optimized (without BatteryLife)"
Important

IF THIS MODE IS CHANGED, THE SYSTEM WILL NOT WORK PROPERLY!

Image

3. Disable scheduled loading

  1. Go to "Settings"
  2. Go to "ESS"
  3. Go to "Scheduled charge levels"
  4. Disable all scheduled charge levels
Image

4. Activate switch

The switch at the bottom of the inverter must be in position 1 to accept the control.

Image

Troubleshooting

If your inverter still is not working properly, please check the following:

  1. Dynamic ESS must be disabled.
  2. Are your grid limits set correctly?
  3. Are your groups set correctly in the controller? (See example below)
  4. If the battery is oscillating, set the scheduler run time to 5s minimum in the advanced settings.
Groups example

If you experience problems with the control of the inverter, please follow these steps:

  1. Before following these steps make sure to remove the Victron inverter from the SmartgridOne controller so that the controller doesn't interfere with the testing.
  2. Now go to the Victron interface. Under the "Settings" tab, go to "System Setup".
Groups example
  1. Go to "ESS".
Groups example
  1. Press "Grid setpoint".
Groups example
  1. Set the grid setpoint to a certain value so that the battery will start charging or discharging.
Groups example
  1. Validate on the overview page that the battery is charging or discharging.
Groups example
  1. If there is no response to the setpoint then this indicates there is an issue with the Victron inverter, rather than the SmartgridOne controller."