ApparatenPV hybrid and battery inverters
Regitec Omvormers
Ondersteunde Apparaten
De SmartgridOne Controller ondersteunt Regitec Hybride omvormers via zowel Modbus TCP (Ethernet) als Modbus RTU (RS485).
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Regitec Hybride Omvormer | ✅ | ✅ |
Bekabeling
Ethernet
Voor correcte ethernetbekabeling: Volg de richtlijnen voor ethernetbekabeling.
RS485
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| A | RS485 A | RS485_POS | RS485 A | TX+ |
| B | RS485 B | RS485_NEG | RS485 B | TX- |
| GND | RS GND | GND | Not available | G |
Note
Zorg ervoor dat de terminatieweerstand correct is ingesteld als de omvormer aan het einde van de RS485-bus staat.
Warning
De Regitec driver is strikt geconfigureerd voor een Baud Rate van 9600. Zorg ervoor dat de omvormer niet is ingesteld op 19200 of 115200, aangezien dit communicatie zal verhinderen.