ApparatenPV hybrid and battery inverters
Sunwoda
Ondersteunde Apparaten
| Device Type | Modbus TCP (Ethernet) | RS485 | Curtailment |
|---|---|---|---|
| OSP-100K-A | ✅ | ✅ | ❌ |
| OSP-200K-A | |||
| OSP-200K-A2 | |||
| OSP-300K-A3 | |||
| OSP-400K-A2 | |||
| OSP-400K-A4 | |||
| OSP-100K-B | |||
| OSP-200K-B | |||
| OSP-200K-B2 | |||
| OSP-100K-C-2 | |||
| OSP-100K-C-3 | |||
| OSP-200K-C | |||
| OSP-200K-C2 | |||
| OSP-100K-H-2 | |||
| OSP-100K-H-3 | |||
| OSP-200K-H | |||
| OSP-200K-H2 |
Caution
Belangrijk voor batterijen groter dan 100 kW
Als uw batterijvermogen is beoordeeld op 100 kW of meer, neem dan contact op met de Sunwoda ondersteuning om het register voor vermogensbeperkingen te vergroten.
Standaard is de vermogensbeperking ingesteld op 100 kW. Dit kan door de Sunwoda ondersteuning worden bijgewerkt op register 0x78f6. SmartgridOne Controller kan vervolgens de vermogensbeperking regelen.
Bekabeling
Ethernet
Voor correcte ethernet bekabeling: Volg de richtlijnen voor ethernet bekabeling.
RS485
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| RS485 A | RS485_POS | RS485 A | TX+ | |
| RS485 B | RS485_NEG | RS485 B | TX- | |
| RS GND | GND | Not available | G |
Configuratie
Als u verbinding maakt via TCP, zorg er dan voor dat het apparaat is geconfigureerd om te communiceren met poort 502.
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.