Schneider-Electric IEM 2100-seriens energimätare
Stödda Enheter
IEM 2100 Serien är enfas energimätare.
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Schneider-Electric iEM 2100 Series | ❌ | ✅ |
| Schneider-Electric iEM 2150 | ||
| Schneider-Electric iEM 2155 |

Koppling
IEM 2100 serien kommunicerar via Modbus RTU över RS485.
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| D1 (+) | RS485 A | RS485_POS | RS485 A | TX+ |
| D0 (-) | RS485 B | RS485_NEG | RS485 B | TX- |
| 0V / Skärm | RS GND | GND | Not available | G |
Vänligen hänvisa till enhetsmanualen för exakta pin-platser, eftersom de kan variera något mellan specifika under-modeller (t.ex. iEM2150 vs iEM2155).
Konfiguration
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
Kommunikationsinställningar
Säkerställ att enhetsinställningarna matchar förarens kapabiliteter definierade nedan:
- Baudrate: 9600, 19200, eller 38400 (Standard är ofta 19200)
- Paritet: Even, Odd, eller Ingen
- Stoppbitar: 1
- Databitar: 8
Kontrollera enhetsmanualen om hur du går in i energimätarens konfigurationsmeny för att ställa in Modbus Adress och Baudrate.