ApparatenPV hybrid and battery invertersSunwoda
Sunwoda
Ondersteunde Apparaten
| Device Type | Modbus TCP (Ethernet) | RS485 | Curtailment |
|---|---|---|---|
| OSP-100K-A | ✅ | ✅ | ❌ |
| OSP-200K-A | |||
| OSP-200K-A2 | |||
| OSP-300K-A3 | |||
| OSP-400K-A2 | |||
| OSP-400K-A4 | |||
| OSP-100K-B | |||
| OSP-200K-B | |||
| OSP-200K-B2 | |||
| OSP-100K-C-2 | |||
| OSP-100K-C-3 | |||
| OSP-200K-C | |||
| OSP-200K-C2 | |||
| OSP-100K-H-2 | |||
| OSP-100K-H-3 | |||
| OSP-200K-H | |||
| OSP-200K-H2 |
Caution
Belangrijk voor batterijen groter dan 100 kW
Als uw batterijvermogen is ingesteld op 100 kW of meer, neem dan contact op met de Sunwoda-ondersteuning om het vermogenslimiteringsregister te vergroten.
Standaard is de vermogenslimitering ingesteld op 100 kW. Dit kan door de Sunwoda-ondersteuning worden bijgewerkt op register 0x78f6. SmartgridOne Controller zal dan in staat zijn om de vermogenslimitering te regelen.
Bekabeling
Ethernet
Voor correcte ethernetbekabeling: Volg de richtlijnen voor ethernetbekabeling.
RS485
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| RS485 A | RS485_POS | RS485 A | TX+ | |
| RS485 B | RS485_NEG | RS485 B | TX- | |
| RS GND | GND | Not available | G |
Configuratie
Als u verbinding maakt via TCP, zorg er dan voor dat het apparaat is geconfigureerd om te communiceren via poort 502.
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.