عدادات الطاقة Schneider-Electric IEM 2100 Series
الأجهزة المدعومة
إن سلسلة IEM 2100 هي عدادات طاقة أحادية الطور.
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Schneider-Electric iEM 2100 Series | ❌ | ✅ |
| Schneider-Electric iEM 2150 | ||
| Schneider-Electric iEM 2155 |

التوصيل
تتواصل سلسلة IEM 2100 عبر Modbus RTU باستخدام RS485.
معلومات
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| D1 (+) | RS485 A | RS485_POS | RS485 A | TX+ |
| D0 (-) | RS485 B | RS485_NEG | RS485 B | TX- |
| 0V / Shield | RS GND | GND | Not available | G |
يرجى الرجوع إلى دليل الجهاز لمعرفة مواقع الأطراف الدقيقة، إذ قد تختلف قليلًا بين الطرازات الفرعية المحددة (مثل iEM2150 وiEM2155).
التكوين
تحذير
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
إعدادات الاتصال
تأكد من تطابق إعدادات الجهاز مع إمكانات برنامج التشغيل المحددة أدناه:
- معدل البود: 9600 أو 19200 أو 38400 (غالبًا ما يكون الإعداد الافتراضي هو 19200)
- التكافؤ: زوجي أو فردي أو بدون تكافؤ
- بتات التوقف: 1
- بتات البيانات: 8
راجع دليل الجهاز لمعرفة كيفية الدخول إلى قائمة تكوين عداد الطاقة لضبط عنوان Modbus ومعدل البود.
Last updated December 10, 2025Edit this page