SmartgridOne logo
SmartgridOne logo
Démarrage rapideInstallationRéseauDirectives de câblage et de connectivitéApp
AperçuNouvelles intégrations
a-TroniXABBAlfenAlpitronicAutelBlitz-PowerEaseeEnovatesEtrelFLEXeCHARGEGo-eHuawei SChargerIlumenKempowerAmtronStations de Charge EV MyEnergiOCPPStations de Charge EV PeblarRaedianSchneider ElectricSiemensSMASofarStations de Recharge EV TeltonikaVolt-TempsStations de Charge EV WallboxZaptec
SpécificationsLEDs de statutTemps de réponse de contrôleTutoriels vidéoCertificatsLicenceSécurité, maintenance et avis légaux
AppareilsEV charging station

Kempower Charging Stations

Kempower

Supported Devices

Device TypeVariantsModbus TCP (Ethernet)RS485
Kempower ChargerAll models supporting Modbus TCP Interface✅❌

Configuration and Interface Details

The Kempower Charging Station uses Modbus TCP as the communication basis.

To ensure communication with the SmartgridOne Controller, note the following:

  1. Connection Requirements: Connections are only allowed from the same subnet the charging station is connected to.
  2. Modbus Port: The standard Modbus Port used is 502.
  3. Maximum Connections: The maximum number of simultaneous connections is 10.

Power Limit Management

The Kempower Charging Station accepts power limit control only via the Modbus TCP interface when Modbus messages are detected.

  • OCPP Conflict: OCPP power limitation messages are not accepted when Modbus is used.
  • Fallback Power: The maximum power used when communication times out reverts to the Fallback Power (W) setting. This power is also used at startup until the Assigned Maximum Power has been received.
  • Minimum Power: Any power limit values below 1000W are interpreted as 0W, which effectively stops charging.