Inversores Sofar TL-G3 y Series TLM/X-G3
Dispositivos compatibles
| Device Type | Modbus TCP (Ethernet) | RS485 | Curtailment |
|---|---|---|---|
| ... | ✅ | ✅ | ✅ |
Advertencia
Advertencia
- La mayoría de los dispositivos pueden comunicarse usando modbus TCP. Esto no es válido para la serie "SOFAR 1...40KTL"
- Algunos inversores requieren firmware específico que está limitado a ciertos distribuidores. Consulte a su distribuidor en caso de dudas.

Cableado
Ethernet
Conecte el inversor a su red de internet usando el "SOFAR SOLAR ETHERNET STICK LSE3".
Para un cableado correcto de ethernet: Siga las .
RS485
...TL-G3 & G1 & G2
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| RS485s TR+ | RS485 A | RS485_POS | RS485 A | TX+ |
| RS485s TR- | RS485 B | RS485_NEG | RS485 B | TX- |
| N/A | RS GND | GND | Not available | G |

...TLX & TLM
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| RS485s TR+ (pin 1) | RS485 A | RS485_POS | RS485 A | TX+ |
| RS485s TR- (pin 3) | RS485 B | RS485_NEG | RS485 B | TX- |
| N/A | RS GND | GND | Not available | G |

Configuración
RS485
Advertencia
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.
El control externo del inversor debe activarse en el menú de configuración del inversor a través de la pantalla LCD.
- Pulse brevemente el botón hacia abajo.
- Verá "1. Enter settings", mantenga pulsado el botón hacia abajo durante 2 segundos para entrar en la configuración.
- Navegue por la configuración hasta que vea:
- Modbus Address o
- Set ComProtocol
- Mantenga pulsado el botón hacia abajo durante 2 segundos para establecer la dirección.
- Ajuste la dirección al valor deseado.