Inverter Delta
Dispositivi Supportati
| Device Type | Variants | Modbus TCP (Ethernet) | RS485 | Curtailment |
|---|---|---|---|---|
| Delta RPI | M6/M8/M10/M12/M15A/M20A/M30 | ❌ | ✅ | ✅ |
| H3/H5/H3A/H4A/H5A (non testati) | ||||
| M6A/M8A/M10A/M50A/M30A (non testati) |
Cablaggio
I SmartgridOne Controller e gli inverter Delta comunicano tramite RS485.
RS485

| Impostazione | opzioni |
|---|---|
| Baudrate | 2400 / 4800 / 9600 / 19200 (default) / 38400 |
| Bit dati | 8 |
| Parità | Nessuna |
| Bit di stop | 1 |
Configurazione
Avviso
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the SmartgridOne Controller will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The SmartgridOne Controller will scan on those first.